• No results found

A heat pump is an energy system that transfers heat from a heat source to a heat sink by use of external work. There are several different heat pump configurations which can be used for various purposes. Among them the vapor compression cycle (VCC), which is often referred to as the typical heat pump. The VCC has a working fluid circulating in a closed cycle where the main components are the compressor, the expansion valve, the condenser, and the evaporator, as shown in figure 2.1. The VCC is shown in a pressure-enthalpy (log p-h) diagram and in a temperature-entropy (T-s) diagram in figure 2.2.

The working principle of the VCC is:

• 1-2: A mechanical compressor sucks low pressure gas out of the evaporator, increasing the pressure and the temperature. The compressor is used to control the pressure difference between the evaporator and the condenser to

Figure 2.1: Simple vapor compression cycle configuration. The blue arrows de-scribe the energy transfer.

50 150 250 350 450 550 650 750

Specific Enthalpy [kJ/kg]

3 10 45

Pressure [bar]

4

3 2

1

1,0 1,5 2,0 2,5 3,0

Specific Entropy [kJ/kgK]

-25 0 25 50 75 100

Temperature [°C]

4 3

2

1

Figure 2.2: Log p-h diagram and T-s diagram for a typical simple vapor compres-sion cycle.

maintain the proper phase change temperatures to interact with the heat source and heat sink. The compressor is driven by mechanical work, which can be supplied by e.g. an electric motor or a diesel engine. Ideal compression is isentropic, which implies that the process is both adiabatic and reversible, i.e. no friction loss or heat transfer out of the system, and is described by:

is= ˙mR·(h2−h1) (2.1)

2.1 Heat pumps Where ˙mRis the working fluid mass flow and ˙Wisis the isentropic compressor work. Real life applications of compression will not be isentropic, and an isentropic efficiency should therefore be defined. The real compression work can then be expressed as a function of the isentropic efficiency as follows:

real= W˙is

ηis

(2.2) Whereηisis the isentropic efficiency.

• 2-3: The compressor discharges the gas into the condenser, where heat is rejected to a heat sink through condensation of the working fluid. The deliv-ered heat is more useful and at a higher temperature than the heat source.

The delivered amount of heat is the sum of the heat absorbed in the evapo-rator and the work input to the compressor, or in other words, the working fluid mass times the enthalpy difference over the condenser, described by:

c= ˙Q0+ ˙Wcomp= ˙mR·(h2−h3) (2.3) Where ˙Q0 is the heat absorbed in the evaporator and ˙Wcomp is the work performed by the compressor on the working fluid.

• 3-4: The high pressure liquid at the end of the condenser is expanded, by use of an expansion valve, to the low pressure of the evaporator. The expansion is assumed to be an isenthalpic process, i.e.:

h3=h4 (2.4)

• 4-1: Heat is transferred from the heat source to the working fluid in the evaporator through evaporation of the working fluid, which is assumed to be an isotherm process, i.e. the temperature is constant. The amount of heat transferred in the evaporator is equal to the working fluid mass flow times the enthalpy difference over the evaporator:

0= ˙mR·(h1−h4) (2.5)

To express the performance of such a system it is common to use the coefficient of performance (COP). The COP is a dimensionless ratio of useful thermal energy over power input to the system, thus the amount of work added to the cycle influences the COP. The COP is defined as in equation (2.6).

COP = Q˙c

comp

(2.6)

The simple VCC also contains a liquid receiver, placed at the outlet of the con-denser and upstream the expansion valve. The liquid receiver stores high pressure liquid leaving the condenser, and it can collect fluid when load fluctuations occur.

It is sized to contain the whole working fluid charge when the heat pump is not in operation. [Grassi, 2018]

The compressor must be able to operate at loads differing from its design point.

The simplest control method is on/off, but this is also very energy consuming.

In addition, the amount of starts and stops for the compressor should be limited to avoid excess stresses on the compressor and the electric motor. Techniques that make it possible to operate the compressor at part load have therefore been developed. For piston compressors this can be done by deactivating some of the cylinders, by bypassing some of the fluid from suction to discharge of the cylinder through signal submission to the solenoid valve. This way, there will be a stepwise reduction in activated cylinders and capacity. Another method is changing the rotational speed of the driving motor. Electric heat pumps often use an inverter to change the feeding frequencies. This will give a more continuous operation and result in increased COP. [Grassi, 2018]

In conjunction with heat pumps there are some terms that are important to un-derstand. In this paragraph some of the terms used later in this master’s thesis are explained using figure 2.3. The evaporation and the condensation process hap-pen in the two-phase region, which is enclosed under the dome in figure 2.3. The compression happens in the vapor region, where also the desuperheating process happens. Desuperheating means cooling of the discharge gas at constant temper-ature to the saturated gas line. In figure 2.3 the critical point is marked, which is the point where the boiling point curve meets the dew point curve. It is only below this point that a liquid and its gas can coexist. In conjunction with heat pumps, the critical temperature and critical pressure is often mentioned, which is the temperature and the pressure at the critical point. In a heat pump system, subcooling means cooling of the liquid out of the condenser at a constant pressure below the saturation temperature in the liquid region. Subcooling happens in the liquid region.