• No results found

Understanding the Transient Stability by Analysing the Original System

CHAPTER 4. UNDERSTANDING THE TRANSIENT STABILITY BY ANALYSING THE

4.3 Equal Area Criterion

+K3 (4.16)

Usingδs0pre the unstable equilibrium point (u.e.p.) δu0pre can be found as δu0pre =π+K3−arcsin

Pref −K1ppre K2pre

=π−δs0pre+ 2K3 (4.17) From the conclusions related to theK’s it is evident that the pre- and post-fault states are identical when using the classical model, and thus the equilibrium points of the two states are also identical as long as the power referencePref is constant, i.e.

δpres0posts0 δpreu0postu0 4.2.2.2 Using the AVR Model

When using the AVR model the pre-fault system will be identical to the pre-fault system when using the classical model and thus the pre-fault e.p.’s are still calculated using (4.16) and (4.17).

However, as E is now changing, the K’s need to be continuously updated withE given by the dynamics both during fault and post-fault, and the known pre-fault value ofEis therefore denoted Epre. This also implies that the e.p.’s of the post fault system will depend on E as given by the dynamics. Lastly, sinceE is a known quantity in the pre-fault state andω=ωnin steady-state, the initial value ofMfipref is found as

Mfipref = Epre

ω (4.18)

4.3 Equal Area Criterion

With the system dynamics modelled analytically, it is possible to start the stability investigation.

Such an investigation typically seeks to determine two parameters that is of particular interest, namely the Critical Clearing Angle (CCA),δcc, and the corresponding Critical Clearing Time

(CCT)tcc. The critical clearing time is the maximum permissible duration a fault can last for which the system will remain stable after the fault. As such it is the time it takes from the initialisation of the fault untilδreaches the critical angleδcc, after which the system will not be able to regain steady-state. To determineδcc and the correspondingtcc, mainly two methods are used in the classical stability assessment, and the first method that will be adopted to the VSM is known as the Equal Area Criterion (EAC).

The EAC is commonly adopted in transient stability analysis of SG’s by using the classical model without dampening, and the dynamics in (4.9) will therefore be considered in this section.

4.3.1 Introduction to the EAC

The Equal Area Criterion can be explained intuitively using theP −δcurve depicted in Figure 4.3, where the pre- and post-fault states are identical as per the problem formulation and the chosen dynamics. A more in-depth explanation can be found in [58].

During pre-fault the system is steady, operating atδs0 in point1. A fault then lowers the grid voltage, and the operating point moves from point1on curve I to point2on curve II. By recalling the analysis in Section 2.8.2, asPref > Pethe virtual rotor will accelerate according to the swing equation. The operating point will then move along curve II from point2to point3where the fault is cleared atδ =δc. The operating point then jumps to point4on curve I, wherePref < Pe. Again, recalling the analysis in Section 2.8.2, the rotor angle will decelerate until point5where

∆ω = 0andδ =δmax, before accelerating back towardsδs0in point1. The angleδmaxis thus the maximum angle of the post-fault system, and it is known thatδmax < δu0 yields a stable post-fault system asδmoves back towards the s.e.p. instead of diverging.

Figure 4.3: TypicalP −δcurve, modified from [56].

As will be shown, the mathematical derivation of the EAC involves integration of powers. As such, it is evident that the EAC uses energy as an instrument to determine for which clearing

angles δc the system will remain stable. Using the discussion above we define the areas Aa and Ad in Figure 4.3 as the acceleration area and the deceleration area respectively. Aa will then represent the injected kinetic energy during fault, whileAdwill represent the ability of the system to absorb energy. For the system to remain stable, it should be able to absorb all the power that is being injected during fault. This can be used to define the EAC; the system will remain stable as long as the deceleration area is equal to, or larger, than the acceleration area, i.e Ad ≥Aa.

The mathematical derivation used to perform a stability analysis using the above-explained concept of the Equal Area Criterion is provided in Section 4.3.2.

4.3.2 Mathematical Derivation

From the introduction to the EAC it is evident that a condition for the system to remain stable is that at at some time ta after the fault has been cleared the system reaches a state where

dt = ∆ω(ta) = 0 before reaching the unstable angle. This can be used to derive the EAC mathematically, and the following derivations will largely follow the discussion in [34].

With the dynamics given by the classical model without dampening from (4.9), the swing equation is given as

It is now possible to multiply both sides with dt = ∆ωyielding

∆ωd∆ω

Next, by integrating this expression,∆ω(ta)can be found in (4.19) through the following steps:

Z ∆ω(ta)

Recalling that dt = ∆ω(ta) = 0must be satisfied for the system to remain stable yields equation (4.20). The system can then be classified as stable if there exists an angleδ=δmax so that the condition in (4.20) holds[34].

Equation 4.20 can be used to define the previously explained acceleration- and deceleration areas.

This is done by definingδ=δcas the clearing angle of the VSM when clearing the fault at the clearing timetc. Equation (4.20) is then reformulated as in (4.21) using the fault- and post-fault quantities, whereAarepresents the acceleration area andAdrepresents the deceleration area.

Z δc Criterion. From Section 4.3.1 and Figure 4.3 it is clear that the maximum deceleration area available is obtained when the maximum angle is the unstable e.p. of the post-fault system, i.e. δmax = δu0post. The critical clearing angleδcc can then be found as the angle fulfilling the condition in (4.22) withδmaxu0post. The critical clearing angle fulfilling the above condition is then found by solving f(δcc) = Aa−Ad,max = 0, typically by using software such as MATLAB. The expressions in (4.23a) and (4.23b) are therefore derived from (4.22) to simplify software implementation.

Aa = (Pref −K1pf )(δcc−δpres0 ) +K2fh Withδccfound, it is of interest to find the correspondingtcc. However, using the EAC, this will only be possible if the electrical power is constant during the fault, i.e. Pef =constant. This will only be the case ifK2f = 0. OtherwisePef will vary withδwhich is changing according to the dynamics. AsEis considered constant in the classical model, the only scenario yielding K2f = 0is a fault whereVgf = 0. If this is the case, the electrical power during fault is given by K1pf and the critical clearing timetcccan be found analytically using (4.24) which is derived by using the the swing equation in the following way:

d∆ω

⇒δcc−δs0pre = Sb

nJ

Pref −Pef

t2cc

tcc =

s 2ωnJ

Sb(Pref −Pef)(δcc−δpres0 ) (4.24) For situations where K2f 6= 0the critical clearing time cannot be found analytically using the EAC, and other methods must therefore be applied. Thus the Equal Area Criterion has been adopted to the Synchronverter VSM to find the critical clearing angle and, if possible, the critical clearing time. This concludes the stability analysis using the EAC.