• No results found

Electromagnetic Oscillation Origin Location in Multiple-Inverter-Based Power Systems Using Components Impedance Frequency Responses

N/A
N/A
Protected

Academic year: 2022

Share "Electromagnetic Oscillation Origin Location in Multiple-Inverter-Based Power Systems Using Components Impedance Frequency Responses"

Copied!
20
0
0

Laster.... (Se fulltekst nå)

Fulltekst

(1)

Digital Object Identifier XX.XXXX/YYY.20XX.ZZZZZZZ

Electromagnetic Oscillation Origin

Location in Multiple-Inverter-Based Power Systems Using Components Impedance Frequency Responses

WEIHUA ZHOU1, (Student Member, IEEE), RAYMUNDO E. TORRES-OLGUIN2,

MEHDI KARBALAYE ZADEH3, (Member, IEEE), BEHROOZ BAHRANI4, (Senior Member, IEEE), YANBO WANG1, (Senior Member, IEEE), and ZHE CHEN1, (Fellow, IEEE)

1Department of Energy Technology, Aalborg University, 9220 Aalborg, Denmark (e-mail: wez@et.aau.dk; ywa@et.aau.dk; zch@et.aau.dk)

2SINTEF Energy Research Institute, 7034 Trondheim, Norway (e-mail: raymundo.torres-olguin@sintef.no)

3Department of Marine Technology, Norwegian University of Science and Technology, 7491 Trondheim, Norway (e-mail: mehdi.zadeh@ntnu.no)

4Department of Electrical and Computer Systems Engineering, Monash University, 3800 Clayton VIC, Australia (e-mail:behrooz.bahrani@monash.edu) Corresponding author: Zhe Chen (e-mail: zch@et.aau.dk).

This work was supported by the ForskEL and EUDP project “Voltage Control and Protection for a Grid towards 100% Power Electronics and Cable Network (COPE)” (Project No.: 880063).

ABSTRACT

Existing impedance-based stability criterion (IBSC) for electromagnetic stability assessment of multiple-grid- connected-inverter (GCI)-based power systems suffers from several limitations. First, global stability feature is hard to be obtained if Nyquist-criterion-based IBSC is used. Second, heavy computational burdens caused by either right-half-plane (RHP) poles calculation of impedance ratios or nodal admittance matrix construction can be involved. Third, it’s not easy to locate the oscillation origin, since the dynamics of individual components are missing in the aggregated load and source sub-modules. This article aims to overcome the aforementioned three limitations of the existing IBSC. First, frequency responses of the load impedance and source admittance defined at each node in a selected components aggregation path are obtained by aggregating individual components (e.g., GCIs and transmission lines), from which imaginary parts of RHP poles of these load impedances and source admittances are directly identified without knowing analytical expressions of these load impedances and source admittances. Then, based on the Nyquist plots of minor loop gains (defined as the ratios of the impedance frequency responses of these load and source sub-modules), stability features of these selected nodes are obtained. Finally, if some nodes are unstable, the oscillation origin is located based on numbers of the RHP poles of these load impedances and source admittances. Compared to the existing IBSC, the presented method can assess global stability and locate oscillation origin more efficiently. The local circulating current issue, as a main obstacle of the existing IBSC, can also be identified. Time-domain simulation results in Matlab/Simulink platform and real-time verification results in OPAL-RT platform of a four-GCI-based radial power plant validate the effectiveness of the presented electromagnetic oscillation origin location method.

INDEX TERMS Circulating current, impedance frequency responses, grid-connected inverter, impedance- based stability criterion, oscillation origin location.

Nomenclature Abbreviations

AIM Analytical impedance model.

GCI Grid-connected inverter.

IBSC Impedance-based stability criterion.

IFRs Impedance frequency responses.

LIM Loop impedance model.

MLG Minor loop gain.

NAM Nodal admittance model.

NC Nyquist criterion.

P.u.l. Per-uint-length.

PCC Point of common coupling.

PLL Phase-locked loop.

RHP Right-half-plane.

TL Transmission line.

(2)

VF, MF Vector fitting and matrix fitting al- gorithms.

Symbols

ω1 Grid fundamental angular fre-

quency.

Cf Filter capacitance.

fsw,fs,Ts Switching frequency, sampling fre- quency, and sampling time.

Ig,Ig Grid current and its reference.

Ig,dref,Ig,qref The d-axis and q-axis grid current references.

IK,IK Output current of GCI #K and its reference.

Kcp Capacitor-current-feedback coeffi- cient.

Kppll,Kipll Proportional and integral gains of the PLL regulator.

Kp,Ki Proportional and integral gains of the current regulator.

Lf1,Lf2 Inverter-side and grid-side filter in- ductances.

SNlef t

K,INlef t

K,YNlef t

K Norton equivalent circuit of the left part of nodeNK.

SP CClef t ,IP CClef t ,YP CClef t Norton equivalent circuit of the left part of PCC.

SNright

K ,VNright

K ,ZNright

K Thevenin equivalent circuit of the right part of nodeNK.

SP CCright,VP CCright,ZP CCright Thevenin equivalent circuit of the right part of PCC.

Vdc DC-link voltage.

YNf rrl0 K ,ZNf rrr0

K The admittance and impedance fre- quency responses by seeing left- ward and rightward at the right side of nodeNK0 .

YNrl0 K,ZNrr0

K,YNf rrl0 K ,ZNf rrr0

K The admittance and impedance models by seeing leftward and rightward at the right side of node NK0 , and their frequency resposnes.

INGCI

K ,YNGCI

K Current source and admittance of the Norton equivalent circuit of GCI

#K.

SNbot0 j,INbot0

j,YNbot0

j Norton equivalent circuit of the bot- tom part of nodeNj0.

SNlef t0 j

,INlef t0 j

,YNlef t0 j

Norton equivalent circuit of the left part of nodeNj0.

SNlr0 j,VNlr0

j,ZNlr0

j Thevenin equivalent circuit by see- ing rightward at the left side of node Nj0.

SNright0 j ,VNright0

j ,ZNright0

j Thevenin equivalent circuit of the right part of nodeNj0.

SNrl0 j,INrl0

j,YNrl0

j Norton equivalent circuit by seeing leftward at the right side of nodeNj0. TNclm1

K ,TNm1

K Closed and open MLGs between

SNlef t

K andSNright

K at nodeNK.

TP CCclm1,TP CCm1 Closed and open MLGs between SP CClef t andSP CCrightat PCC.

TNclml0 q ,TNclmr0

q Closed MLGs between SNright0 q and SNbot0

q, and between Z2q−2 andSNrl0 q

at nodeNq0. TNclmrl0

K

Closed MLG between SrightN0 K

and SNlef t0

K

at nodeNK0 . TNclm0

K,TNm0

K Closed and open MLGs between

SNrl0 K

andSNright0 K

at nodeNK0 . TNclm

p Closed MLG between Z2p−1 and

GCI #p at nodeNp. I. INTRODUCTION

Recently, renewable energies, such as wind power and solar power, have been increasingly penetrating into the exist- ing utility grid [1]. Voltage source grid-connected inverters (GCIs), as efficient power electronic interfaces, are widely used to transmit the generated electricity into the utility grid [2]. However, impedance interactions between various con- trol loops of the GCIs (e.g., outer power control loop, dc-link voltage control loop, inner current control loop, and phase- locked loop (PLL)) and passive components (e.g., trans- mission lines (TLs), underground cables, and transformers) may cause electromagnetic oscillation phenomena in various frequency ranges [3]–[6]. Though oscillation mechanisms of single-GCI-based power plants have been thoroughly ex- plored in [4], [7]–[11], the oscillation mechanism and oscilla- tion origin location of multiple-GCI-based power plants need to be further investigated.

Impedance-based stability criterion (IBSC) was originally proposed in [12] to assess the stability of DC power systems, and then modified in [13], [14] to cope with AC power systems. The whole power plant is partitioned into load and source sub-modules at an arbitrary node, based on which impedance ratio of the load and source sub-modules is cal- culated. Both encirclement number of Nyquist plot of the impedance ratio around (−1, j0) and number of right-half- plane (RHP) poles of the impedance ratio should be calcu- lated [14], [15]. For single-GCI-based power plants, RHP poles calculation can be avoided, since both the GCI and the grid should be inherently stable [10], [14]. Furthermore, if the system is assessed as unstable, the oscillation origin can be located as the impedance interaction between the GCI and the grid. However, avoidance of RHP poles calculation and loca- tion of oscillation origin commonly cannot be achieved in multiple-GCI-based power plants by performing the Nyquist criterion (NC) one time at a selected node, since RHP poles may emerge during the components aggregation procedure, and the oscillation origin may be lost in the aggregated load and source sub-modules [16]–[18].

The RHP poles of the aggregated load and source sub- modules can be analytically derived based on system topol- ogy and impedance transfer functions of individual com- ponents [16], [17], [19]. However, this analytical approach

(3)

sometimes cannot be implemented in practice, since internal structures and parameters of the GCIs can be confidential due to industry secrecy. In addition, the orders of the load and source sub-modules may be very high if a huge number of GCIs exist in the power plant, which will result in heavy computational burdens. The vector fitting (VF) and matrix fitting (MF) algorithms initially proposed in [20], [21] can fit a set of discrete frequency responses by continuous trans- fer function and transfer matrix, respectively, which have been employed in [18], [22]–[25] to facilitate the stability assessment of power electronic-dominated power systems.

Specifically, the VF algorithm is used in [18], [23] to fit discrete load impedance and source admittance frequency responses as continuous transfer functions, so that extrac- tion of the RHP poles from the analytically-derived transfer functions can be avoided. Discrete loop impedance models (LIMs) are established in [26]–[28] by further aggregating the impedance frequency responses of the load and source sub-modules, based on which the MF algorithm is used to generate continuous LIMs, and zeros of the determinant of the fitted LIMs are identified. Although the RHP poles identification can be more efficient or even avoided with the help of the VF and MF algorithms, oscillation origin still cannot be located.

According to [17], [29], nodal admittance model (NAM) and the aforementioned LIM are dual pairs. Therefore, the zeros of the determinants of system NAMs are calculated in [30]–[32] for stability analysis. Similar to the LIM method, the RHP poles calculation can also be avoided in the NAM method. In addition, a frequency-domain component connec- tion method is presented in [16], [33]–[35], where the gen- eralized NC is applied on the return ratio of the impedance matrices of the connection network and the composite model of all inverters. Since the two impedance matrices can com- monly be guaranteed to not have RHP poles, the RHP poles calculation in the generalized NC can be avoided. According to the discussions in [16], [35], the derived NAMs in [30]–

[32] are exactly the closed-loop transfer function matrices of multiple-input-multiple-output negative feedback systems with feed-forward gain being 1 and feed-back gain being the return-ratio matrices derived in [16], [33]–[35]. Since admittance information of each GCI is stored in the derived NAM and return-ratio matrix, global stability feature can be obtained, and oscillation origin can further be located based on participation factor analysis [35]. However, orders of both the NAM and the return-ratio matrix can be high, which may lead to heavy computational burdens. In addition, once GCIs are added/removed into/from the power plant or system topology changes, the high-order NAM and return- ratio matrix should be re-calculated.

The NC and generalized NC are sequentially implemented from the farthest node to point of common coupling (PCC) of radial power plants in [36], [37] and [19], [38], [39], respec- tively. No RHP poles calculation is needed, since both load and source sub-modules are inherently stable in each step. In addition, the node where the (generalized) NC is not satisfied

is identified as the oscillation origin. Compared with the LIM, NAM, and component connection method, the multiple-step stability analysis method is more flexible, and can reduce the computational burdens. However, only stability of grid current instead of output currents of individual GCIs can be assessed, i.e., this analysis method cannot obtain global stability feature. Furthermore, the presented conditions in [19], [36]–[39] to guarantee the stability of grid current are sufficient yet not necessary.

To fill in the research gaps mentioned in the above lit- erature review, a computationally efficient global stability analysis and oscillation origin location method based on only terminal impedance frequency responses of individual com- ponents is presented in this article. First, terminal impedance frequency responses of individual components are aggre- gated at both sides of each node in a selected components aggregation path. On its basis, RHP poles of these load and source sub-modules are directly identified from their impedance and admittance frequency responses, respectively.

The stability of these selected nodes is then obtained with further help of the Nyquist plots of the impedance ratios. If a specific node is unstable, the oscillation origin is located based on numbers of RHP poles of these load and source sub- modules. Main contributions of this article can be highlighted as follows.

1) An NC-based sufficient and necessary condition for global stability is derived, where relation between global stability and local stability is discussed.

2) Based on the derived NC-based global stability con- dition, an efficient oscillation origin location method is presented. The problematic nodes where RHP poles occur during components aggregation can be identified.

3) RHP poles of load and source sub-modules for the NC are directly identified from load impedances and source ad- mittances frequency responses, respectively, without know- ing analytical expressions of load and source sub-modules, which can reduce the computational burdens and cope with black-box models.

4) Circulating current phenomenon is identified based on numbers of RHP poles of the load and source sub-modules along the selected components aggregation path.

5) A grid current stability enhancement method is initiated, i.e., the paralleled stable branch of an unstable branch is enforced to be the same as the unstable branch, which may be achieved by adjusting the transmission line impedance of the stable branch.

The rest of this article is organized as follows. In Section II, an NC-based sufficient and necessary condition for global stability of a representative radial power plant is derived.

On its basis, the principle and implementation procedure of the presented global stability analysis and oscillation origin location method are explained in Section III. In Section IV, the presented method is implemented in a four-GCI- based radial power plant. The correctness of the theoretical analysis results in Section IV is validated in Section V. In Section VI, comparisons between the presented method and

(4)

M

left YN

M

right

ZN Vg

Zg

GCI #M GCI #4 GCI #3 GCI #2 GCI #1

+

-

0') ( PCC N

GCI NM

Y 4

GCI

YN 3 GCI

YN 2 GCI

YN 1 GCI

YN

GCI NM

I IGCIN4 INGCI3 IGCIN2 IGCIN1

NM N4 N3 N2 N1

4

left YN

4

right ZN

3

right ZN ZNright2

1

right ZN

3

left YN

2

left YN

1

left YN

IM I4 I3 I2 I1

2M1

Z 2M2 Z

Z7

Z6

Z5

Z4

Z3

Z2

Z1

Z0 '

NM N4' N3' N2' N1'

2 2

( M )

I Z I Z( )6 I Z( )4 I Z( )2 I Z( )0 Ig PCCleft Y ZPCCright

FIGURE 1. Equivalent circuit model of a representative radial grid- connected power plant [40].

existing IBSCs are performed. Finally, Section VII draws the conclusion.

II. AN NC-BASED SUFFICIENT AND NECESSARY CONDITION FOR GLOBAL STABILITY

Fig. 1 shows the single-line diagram of a radial grid- connected power plant, which consists of M GCIs. The detailed control structure of these GCIs are explained in Appendix A. If grid current Ig and output currents of all GCIs (i.e., I1–IM) are stable, the system is globally stable.

The global stability can be assessed by further simplifying the equivalent circuit model in Fig. 1. The aggregation rules of two components/sub-modules during the circuit simplifi- cation procedure are stated here [18]. Each component/sub- module can be defined as either Y type or Z type which should be modeled as an Norton or a Thevenin equivalent circuit, respectively. In detail, individual GCIs and grid are defined asY type andZtype, respectively. The transmission lines and underground cables are defined asY type in parallel case and Z type in series case. Based on the definitions of individual components, the type of the aggregated sub- module of two components/sub-modules are further defined as follows. The aggregated sub-module is Z type, if two Z-type components/sub-modules are connected in parallel or in series, or oneZ-type component/sub-module and one Y-type component/sub-module are connected in parallel.

Furthermore, the aggregated sub-module is Y type, if two Y-type components/sub-modules are connected in paral- lel, or one Z-type component/sub-module and oneY-type component/sub-module are connected in series.

Based on the components/sub-modules aggregation rules, Fig. 1 can be simplified as Fig. 2(a) by representing the left and right parts of PCC as an Norton and a Thevenin equivalent circuit, respectively. In addition, Fig. 1 can be simplified as Fig. 2(b) by representing the left and right parts of node NK (K ∈ [1, M]) as an Norton and a Thevenin equivalent circuit, respectively. Based on Fig. 2, Ig andIK can be calculated as

Ig=IP CClef t −VP CCrightYP CClef t

1 +ZP CCrightYP CClef t =TP CCclm1Ig (1) and

IK =INlef t

K −VNright

K YNlef t

K

1 +ZNright

K YNlef t

K

=TNclm1K IK (2)

right

VPCC

Ig

right

ZPCC left

YPCC

right

ZPCC

left

YPCC left

IPCC

'

( 0) PCCN

- +

left

SPCC SPCCright

(a)

K right

VN K right

ZN K left

YN

K right

ZN

K left

YN K left

IN

NK +

- IK

K right

SN K

left

SN

(b)

FIGURE 2. IBSC at different nodes of Fig. 1. (a) At PCC. (b) At nodeNK

(K[1, M]).

, respectively, where TP CCclm1 = (1 +ZP CCrightYP CClef t)−1,Ig = IP CClef t −VP CCrightYP CClef t,TNclm1

K = (1 +ZNright

K YNlef t

K )−1, and IK =INlef t

K −VNright

K YNlef t

K . Based on Appendix B, numbers of RHP poles ofIgandIKcan be calculated as

P(Ig) =P(TP CCclm1) =P(TP CCm1 ) +N(−1,j0)(TP CCm1 ) (3) and

P(IK) =P(TNclm1K ) =P(TNm1K) +N(−1,j0)(TNm1K) (4) , respectively, whereP(•)andZ(•)indicate number of RHP poles and RHP zeros, respectively. N(−1,j0)(•) indicates encirclement number of Nyquist plot around (−1, j0) in clockwise direction. In addition,TP CCm1 =ZP CCrightYP CClef t and TNm1

K =ZNright

K YNlef t

K . Since grid and GCI #K(K ∈ [1, M]) are assumed to be inherently stable,ZP CCrightandYNlef t

K do not have RHP poles [14]. However,YP CClef t andZNright

K may have RHP poles (This issue will be discussed in Section III-A.) [15].

A sufficient and necessary condition for the global stability of Fig. 1 can be summarized as follows.

Lemma 1: The radial grid-connected power plant in Fig. 1 is globally stable if and only if

1) Igis stable, i.e.,P(TP CCm1 ) +N(−1,j0)(TP CCm1 ) = 0; and 2) IK (K ∈ [1, M]) is stable, i.e., P(TNm1

K) + N(−1,j0)(TNm1

K) = 0.

III. PRESENTED GLOBAL STABILITY ANALYSIS AND OSCILLATION ORIGIN LOCATION METHOD

In this section, the NC-based sufficient and necessary condi- tion for global stability derived in Section II is reformulated.

On its basis, the principle of the presented global stability analysis and oscillation origin location method is explained.

A. REFORMULATION OF THE NC-BASED SUFFICIENT AND NECESSARY CONDITION FOR GLOBAL STABILITY Based on the components/sub-modules aggregation rules in Section II, the components aggregation procedure of Fig. 1 from left to right is shown in Fig. 3(a), which consists of three main steps at each node. Take nodeNK0 (K ∈[1, M]) as an example. In step 1, Z2K−1and GCI#Kare aggregated as SbotN0

K. In step 2,SNlef t0

K at the left of node NK0 andSbotN0 K at the bottom of nodeNK0 are further aggregated asSrlN0

K (The

(5)

2K1

Z

K GCI

YN K' left

IN

K GCI

IN

2K 2

Z

Step 1 '

NK NK' '

NK

' K left

YN

'K left

SN '

K left

SN ' K left

YN

' K left

IN

' K bot

SN '

K rl

SN K' rl

YN

' K rl

IN

GCI #K

NK 'K

bot

YN

' K bot

IN

1 K K

Step 2 Step 3

' 1

NK

(a)

2K2

Z 2K1

Z

Step 1 Step 2

S ' K bot ' N

S 1 K lr N '

NK

GCI #K NK

' 1

NK NK'

K GCI

IN K GCI

YN

' 1 K lr

ZN

'1 K lr

VN

S ' K right N ' K right

ZN

' K right

VN 'K bot

IN ' K bot

YN 2K1

Z

S ' K right N '

NK

GCI #K

K GCI

IN K GCI

YN

' K right

ZN

' K right

VN

Step 3

NK

1 KK

(b)

FIGURE 3. Components aggregation procedures at nodeNK0 in Fig. 1. (a) From left to right. (b) From right to left.

superscriptrlmeans thatSNrl0

Kis the aggregated sub-module by seeing leftward at the right side of nodeNK0 . In step 3, SNrl0

K andZ2K−2are aggregated as SNlef t0

K−1. The parameters ofSbotN0

K,SNrl0

K, andSNlef t0

K−1are calculated as INbot0

K =TNclm

KINGCI

K YNbot0

K =TNclm

KYNGCI

K (5)

INrl0

K=INlef t0 K

+INbot0

K YNrl0

K =YNlef t0 K

+YNbot0 K (6) and

INlef t0 K−1

=TNclmr0 K INrl0

K YNlef t0 K−1

=TNclmr0 K YNrl0

K (7) , respectively, where TNclm

K = (1 +Z2K−1YNGCI

K )−1 and TNclmr0

K

= (1 +Z2K−2YNrl0 K

)−1. The Norton equivalent circuit of the left part of node NK0 (K ∈ [0, M]) in Fig. 1 can then be derived based on Fig. 3(a) and (5)-(7) using recursive method, shown as

INlef t0 K

=

M

X

p=K+1

(TNclmp INGCIp

p

Y

q=K+1

TNclmr0 q )

YNlef t0 K

=

M

X

p=K+1

(TNclmp YNGCIp

p

Y

q=K+1

TNclmr0

q ) (8)

IP CClef t and YP CClef t in Fig. 2(a) can then be calculated as INlef t0

0 andYNlef t0

0 , respectively. A sufficient yet not necessary condition for stability ofIgcan be derived based on item 1) of lemma 1 and (8), shown as follows.

Lemma 2:Igis stable, if

1) YP CClef t is stable, i.e.,∀p, q∈[1, M],TNclm

p andTNclmr0 q do not have RHP poles; and

' K right

ZN

K GCI

YN 'K

left

IN

K GCI

IN 2K1

Z

'K left

YN

( 2K)

I Z I Z( 2K2) Z '

K rr ' N

K rl

YN

NK

IK '

NK

' K right

VN

S ' K right ' N

S

K left N

GCI #K

+ -

FIGURE 4. Components aggregated at both sides of nodeNK0 .

2) The Nyquist plot ofTP CCm1 does not encircle(−1, j0).

On the other hand, the components aggregation procedure of Fig. 1 from right to left is shown in Fig. 3(b), which consists of three main steps at each node. Take node NK0 (K∈[1, M]) as an example. In step 1,SlrN0

K−1andZ2K−2are aggregated as SNright0

K (The superscriptlrmeans thatSNlr0 K−1

is the aggregated sub-module by seeing rightward at the left side of node NK−10 . In step 2, GCI #K and Z2K−1 are aggregated asSbotN0

K. In step 3,SNright0

K andSNbot0

Kare aggregated asSNlr0

K. In addition to the parameters ofSNbot0

K shown in (5), the parameters ofSNright0

K andSNlr0

Kare calculated as VNright0

K

=VNlr0 K−1

ZNright0 K

=ZNlr0

K−1+Z2K−2 (9) and

VNlr0

K=TNclml0 K (VNright0

K

+ZNright0 K

INbot0 K) ZNlr0

K =TNclml0 K ZNright0

K (10)

, respectively, where TNclml0 K

= (1 +ZNright0 K

YNbot0 K

)−1. The Thevenien equivalent circuit of the right part of node NK0 (K ∈ [1, M]) in Fig. 1 can then be derived based on Fig.

3(b), (5), and (9)-(10) using recursive method, shown as VNright0

K

=TNclml0 0 Vg

K

Y

q=1

TNclml0 q +

K

X

p=1

(TNclm

p INGCI

p (Z2p−2

+ZNright0 p−1)

K

Y

q=p

TNclml0 q )

ZNright0 K =Zg

K

Y

q=0

TNclml0 q +

K

X

p=1

(Z2p−2 K

Y

q=p

TNclml0

q ) (11) Based on the derived Norton and Thevenin equivalent circuits of the left and right parts of nodeNK0 in (8) and (11), respectively, Fig. 1 can be simplified as Fig. 4 at nodeNK0 , which can further be simplified as Fig. 2(b). The parameters ofSNright

K can thus be calculated as VNright

K =TNclmrl0 K (VNright0

K

+ZNright0 K

INlef t0 K

) ZNright

K =TNclmrl0 K ZNright0

K +Z2K−1 (12)

(6)

where TNclmrl0 K

= (1 +ZNright0 K

YNlef t0 K

)−1. P(ZNright

K ) can be calculated as

P(ZNright

K ) =P(ZNright0 K

) +P(YNlef t0 K

) +N(−1,j0)(TNmrl0 K)(13) whereTNmrl0

K = ZNright0 K

YNlef t0 K

. A sufficient yet not necessary condition for stability ofIKcan be derived based on item 2) of lemma 1, (8), (11), and (13), shown as follows.

Lemma 3:IKis stable, if 1) YNlef t0

K

is stable, i.e.,∀p, q∈[K+1, M],TNclm

p andTNclmr0 q

do not have RHP poles; and 2) ZNright0

K is stable, i.e.,∀p, q∈[1, K−1],TNclmp andTNclml0 q

do not have RHP poles; and 3) The Nyquist plot of TNmrl0

K

does not encircle (−1, j0);

and

4) The Nyquist plot ofTNm1Kdoes not encircle(−1, j0).

To not lose the generality, Fig. 5(a) shows a complicated grid-connected power plant with multiple strings. Similar with the stability analysis of Ig and IK (K ∈ [1, M]) in Fig. 1, which needs to calculate YP CClef t in Fig. 2(a) and ZNright

K (K ∈ [1, M]) in Fig. 2(b), respectively, the stability analysis of grid current and output currents of all GCIs in Fig. 5(a) also needs the corresponding aggregated admittance and impedance frequency responses, respectively. Take the stability analysis ofIgandI12as an example. First, a main components aggregation path is selected, shown as the red line in Fig. 5(a), based on which the rest of the whole system can be divided into strings (i.e., strings #1, #3, #5, #6, and

#7) and individual GCIs (i.e., GCIs #2, #4, and #8). Then, the equivalent circuit model of Fig. 5(a) can be established in Fig.

5(b) by applying the components aggregation procedure in Fig. 3(a) to represent the five strings as five Norton equivalent circuits. Fig. 5(b) is in the similar form of Fig. 1, which indicates thatYP CClef t andZNright0

1 in Fig. 5(b) can be calculated using (8) and (12), respectively. Furthermore, the equivalent circuit model of sting #1 can be established as Fig. 5(c) using the derivedVNright0

1 andZNright0

1 , based on which ZNright0 11 can be calculated using Fig. 4. It can be seen that the presented components aggregation procedures in Fig. 3 are the basis for stability analysis of more complicated grid-connected power plants.

B. PRESENTED GLOBAL STABILITY ANALYSIS AND OSCILLATION ORIGIN LOCATION METHOD

The converse-negative propositions of lemmas 2 and 3 can be derived as lemmas 4 and 5, respectively.

Lemma 4: IfIgis unstable, then 1) ∃p, q ∈ [1, M],TNclm

p orTNclmr0

q has at least one pair of RHP poles; or

2) The Nyquist plot ofTP CCm1 encircles(−1, j0).

Lemma 5: IfIKis unstable, then 1) YNlef t0

K is unstable, i.e., ∃p, q ∈ [K+ 1, M], TNclmp or TNclmr0

q has at least one pair of RHP poles; or 2) ZNright0

K

is unstable, i.e.,∃p, q∈[1, K−1],TNclm

p orTNclml0 q

has at least one pair of RHP poles; or

: GCI

'

N1

Utility Grid

'

N2 '

N3 '

N4 '

N5

'

N6

'

N8

PCC

'

N7

'

N11 '

N12 '

N13 '

N14

String #1 String #3

String #5

String #6 String #7 GCI #2

GCI #8

GCI #4 GCI #11 GCI #12

GCI #13 GCI #14

Ig

I12

(a)

Vg

Zg

String #1

+ -

1' N

PCC

GCI #2

2' N

String #3

3' N

GCI #4

4' N

String #5

5' N

String #6

6' N

String #7

7' N

GCI #8

8' N

PCC

Yleft

1' N right

Z

Ig

(b)

+ -

11'

N

GCI #12 12' 13' N N

GCI #14 14'

N N1'

right

Z

11' N right

Z '

N1

right

Z

1' N right

V

GCI #11 GCI #13

I12

(c)

FIGURE 5. Equivalent circuit model of a complicated grid-connected power plant with multiple strings. (a) Topology of the grid-connected power plant.

(b) First equivalent circuit model. (c) Second equivalent circuit model.

3) The Nyquist plot ofTNmrl0

K encircles(−1, j0); or 4) The Nyquist plot ofTNm1

Kencircles(−1, j0).

Items 1) and 2) of lemma 1 show thatZP CCrightandYP CClef t are needed for calculation ofP(Ig), andZNright

K andYNlef t

K are needed for calculation ofP(IK), respectively. The derivation procedure of these impedance/admittance models in the con- ventional IBSCs can be explained as follows [14], [17], [19], [23]. Figs. 3(a) and 3(b) are performed to sequentially estab- lish the Norton and Thevenin equivalent circuits of the left and right parts of nodesNM0 –N00 andN00–NM0 , respectively.

On its basis, the derived Norton and Thevenin equivalent circuits at two sides of nodeNK0 (K∈[1, M]), i.e.,SNlef t0

K

and SrightN0

K

in Fig. 4, are further aggregated asSNright

K . The con- ventional IBSCs suffer from the following three drawbacks.

First, derivations of the analytical expressions of ZP CCright, YP CClef t, ZNright

K , and YNlef t

K for RHP poles calculation may be impossible due to the industry secrecy. Second, ZNright

K

is obtained by further aggregating SNlef t0 K

andSNright0 K

, which may be tedious and bring in heavy computational burdens.

Third, the oscillation origin is difficult to locate, since it is

Referanser

RELATERTE DOKUMENTER

Organized criminal networks operating in the fi sheries sector engage in illicit activities ranging from criminal fi shing to tax crimes, money laundering, cor- ruption,

Recommendation 1 – Efficiency/sustainability: FishNET has been implemented cost-efficiently to some extent, and therefore not all funds will be spent before the project’s

3.1 Evolution of costs of defence 3.1.1 Measurement unit 3.1.2 Base price index 3.2 Operating cost growth and investment cost escalation 3.3 Intra- and intergenerational operating

Based on the above-mentioned tensions, a recommendation for further research is to examine whether young people who have participated in the TP influence their parents and peers in

Scalable and flexible trust models and solutions for trust management must be found, as well as the political and policy foundation for trusting cooperating parties and

Abstract A two-and-a-half-dimensional interactive stratospheric model(i.e., a zonally averaged dynamical-chemical model combined with a truncated spectral dynamical model),

Non-linear time domain global dynamic analysis is performed in in-line direction (direction of oscillation) to simulate the dynamic response in in-line direction.... 87 ×

To account for the effect of frequency-dependent cable parameters on the oscillation modes and damping in small-signal studies, an HVDC cable model based on pi-equivalent sections