• No results found

The automatic voltage regulator

2.2 The excitation system

2.2.2 The automatic voltage regulator

The automatic voltage regulator (AVR) is the main controller of the excitation system. Its responsibility is to observe machine terminal voltage changes and respond accordingly by ad-justing the field voltage. There have been developed guidelines for modelling of AVRs and their associated components for different applications. The Institute of Electrical and Electronics En-gineers (IEEE) has published recommended practices for excitation system modelling [43]. For example, a potential-source fed static excitation system with a PI regulator type AVR can be categorised as an ST7C model.

2.2.2.1 Inputs and outputs

The AVR typically has four inputs:

• The control or compensated voltageVc. This is the measurement of the terminal voltage.

It is not uncommon that the control voltage is compensated to a certain electrical distance away from the machine terminals. This compensation is the job of the load compen-sator in Figure 2.5. An electrical distance of around 0.8 times the step-up transformer’s reactance is not uncommon [36].

• The reference voltageVref. This is the voltage the AVR strives to keep the control voltage at.

• Terminal voltageVt. Even if the terminal voltage is not used as the control voltage, it may be used for limiting purposes as a base value for per-unit conversion.

• PSS contributionVpss. This additional signal from the power system stabiliser aims to in-crease the damping of oscillatory behaviour in the rotor angle. The PSS will be described in Section 2.2.3.

The AVR generally only has a single output. Technically, the output is the pulse train to the thyristor rectifier. However, for modelling purposes, the rectifier can be considered a simple transfer function, and the AVR is said to have the generator field voltage as output. [1]

2.2.2.2 Limiters

In real systems, the machine windings cannot be exposed to overly high currents for too long, as they will get damaged. Therefore, some limiters are implemented into the AVR. There are mainly four limiters:

• The overexcitation limiter (OEL) limits the maximum field current to the machine rotor windings according to their thermal capabilities. Still, the OEL allows for some overcur-rent to flow for an amount of time such that a high field forcing during disturbances is still possible. If the overexcitation lasts too long, the OEL starts to limit the field current to safe levels. [1, 43].

• The underexcitation limiter (UEL) ensures the machine does not become too under-excited. If this occurs, the machine may lose synchronism or associated loss-of-excitation relays may trip.

• The stator current limiter (SCL) protect the stator winding from overcurrents by limiting the field voltage. Since the SCL uses the excitation level to adjust the stator current, it only affects the reactive power flow. Thus, the correct control action to do when the machine is overexcited (capacitive operation) is to reduce the excitation and increase excitation when the machine is underexcited (inductive operation) [1, 43].

• The field voltage limiter limits the output of the AVR to avoid damaging the field wind-ings. This limiter is what determines the field ceiling voltage.

2.2.2.3 The AVR and stability

Consider the generator-infinite bus system in Figure 2.7 [1]. Assuming the internal emfEq is constant andXd=Xq, the air-gap power delivered by the machine is given by:

Pe = EqVs

xd sin(δ) (2.50)

where,

• Pe= The delivered air-gap power of the generator

• Eq = The internal induced voltage of the machine

• Vs = The voltage level at the infinite bus

• xd = Xd+Xt+Xs The sum of the synchronous, transformer and network equivalent reactances

• δ= Power angle of the generator

AVR

V

ref

V

t

Field Generator

V

s

Infinite bus E

q

Figure 2.7: Line diagram of a generator-infinite bus system. The field voltage is determined by the AVR, which uses the terminal voltage to calculate the error from the reference. [1]

Eq being constant implies that there is no AVR action and the system is unregulated. The peak air-gap power occurs at δ = π2. If the load angle increases any further it will result in unstable operation, as further increases in load will result in a decrease in power delivery, see the blue curve in Figure 2.8.

When introducing an AVR the regulator will strive to keep the control voltage constant by adjusting the field current. In a steady-state condition, the power-angle characteristic may look the same as for the unregulated one. However, if a load increase occurs, the stator current will increase, resulting in a larger voltage drop across the internal reactance of the machine. Thus, the terminal voltage will drop. This will be detected by the AVR which will work to increase the generator’s excitation level. When that happens a new, higher power-angle characteristic will be valid. This sequence of events will repeat at further load increases, and reversely so for load decreases. Consequently, the total power-angle curve for a regulated machine will have a shape like the red curve in Figure 2.8 [1, 36]. The regulated power-angle curve is derived from:

Pe= Vs

xdsin(δ) r

xdVt

X 2

−Xd

X Vssin(δ)2

− 1 2

Xd

X Vs2

xdsin(2δ) (2.51) where,

• Pe= The delivered air-gap power of the generator

• Eq = The internal induced voltage

• Vt= Generator terminal voltage

• Vs = The voltage level at the infinite bus

• X =Xt+Xs= The sum of transformer and network equivalent reactances

• xd =Xd+X = The sum of the synchronous, transformer and network equivalent reac-tances

• δ= Power angle of the generator

An AVR will notably increase the amount of power the machine can deliver. The new maximum load angleδmis higher than for the unregulated curve. This means that when a large disturbance happens, like a fault or a line disconnection, the generator has a much higher stability limit and de-acceleration area. Thus, the inclusion of an AVR significantly increases the synchronising torque, and consequently the transient stability of the generator.

Even though the effects of an AVR have positive implications for transient stability, it can be shown that the AVR may introduce negative damping and decrease oscillatory stability. After a disturbance, the generator may keep synchronism after the first rotor swing yet become unstable in an oscillatory fashion after a few swings. The prominence of this negative damping is de-pendent on factors as generator load, AVR gain and network reactance. A large value in any of these enhances the negative damping [36]. Compensating for the negative damping commonly involves introducing an additional control loop to the AVR, called a power system stabiliser.

[1]

Figure 2.8: Air-gap power for both an unregulated and regulated system. This shows that a regulated system (with AVR) has a higher stability limit than an unregulated system (without AVR).